Found Evap Completely Iced Over

On 6/28/2023 Found evap completely iced over. Emptied unit and deiced. Put unit back together and turned on. Found thermostat set to 9 and evap motor turning off and thermostat satisfy. Hardwired evap motor to always run and help deice coil during the off cycle. Set thermostat to 2 and watched box temp reach 37*f and turn off. Customer is happy with that in Austin Hill Texas.