AC fans weren’t running. I found at the wiring for the back hallway unit was wired to be an electric instead of heat pump at the air handler. I removed the wire that did not need to be connected so the fans on and the heater and the unit heated properly 2/28/24 in Austin Texas.…
Read moreInstalled Water Inlet Valve
Installed water inlet valve and made sure it was working properly on 2/27/24 in Austin Texas. Near South Lamar Boulevard Austin, Texas 78704 Check out the Areas We Serve and jobs we are doing by clicking: https://prorefrigerate.com/areas-we-serve/ [spacer][SHORTCODE_ELEMENTOR id=3505]
Read moreCounter Top Cooler Compressor Not Starting
Counter top cooler compressor not starting. Found bad external overload. Removed overload. Compressor started running. Box pulling down on 2/26/24 in Austin Texas. Near San Jacinto Blvd Austin, Texas 78701 Check out the Areas We Serve and jobs we are doing by clicking: https://prorefrigerate.com/areas-we-serve/ [spacer][SHORTCODE_ELEMENTOR id=3505]
Read moreFound a Leak on the Liquid Line King Valve
Found a leak on the liquid line king valve. It was on the body side had to replace the king valve with a 3/8 ball valve and I also replaced the dryer. Once I replaced the bad parts and put in a new filter dryer, I pulled a vacuum on the system and then put…