Drains were clogged causing overflow to fill up shutting the units off outside. I unclogged the drains and had to run a new drain for the front line because it was not sloping properly. The system is cooling down on 5/8/24in Cedar Park Texas. Near N Bell Blvd Cedar Park, Texas 78613 Check out the…
Read moreCooler Defrost Clock was not Working Properly
Cooler Defrost Clock was not working properly Causing the system not to turn on. I replaced the defrost clock and monitored to make sure it pulls down the temp and shuts off on 5/4/24 in Round Rock Texas. Near University Boulevard Round Rock, Texas 78665 Check out the Areas We Serve and jobs we are…
Read moreMoved Sensor to Return Air
Moved sensor to return air. Gaskets good seal 99% very small gap top corner of doors on center post. Condensation around doors is environmentally caused. Controller differential set at 8 degrees adjusted differential to 4 degrees and set fan for continuous on for off cycle defrost. Box pulling down to 33 degrees and cycling off…
Read moreFound Thermostat Wire Disconnected From Time Clock
Found thermostat wire disconnected from time clock. Reconnect wire. Solenoid opened. Unit on and cooling. Set thermostat to 35 on 5/1/24 in Austin Texas. Near San Jacinto Boulevard Austin, Texas 78701 Check out the Areas We Serve and jobs we are doing by clicking: https://prorefrigerate.com/areas-we-serve/ [spacer][SHORTCODE_ELEMENTOR id=3505]