On 6/19/2023 Arrived on site and found that the system was tripped on high head pressure. They had a AC problem yesterday and it got up to 90° in here which could’ve caused it to trip. The AC was fixed yesterday, so I reset the unit and cleaned the condensing coil off and watch the…
Read moreFound Some Open Wires
On 6/16/2023 Washed out with water hose. Reset defrost times and durations. While checking heater amps during defrost I found some open wires (blew up in my face). Caused breaker to trip. Replaced wires and checked defrost amps. 15amp each leg. Customer asked me to stay and deice coil. In the middle of deicing, the…
Read moreCoils Frozen Up and Defrosted the Coil
6/15/2023 found one of the coils frozen up and defrosted the coil, turned the system back on system was running properly. I went to check out the other system and the thermostat on system to put shutting off too soon even though it was set at 35. I replace the thermostat and waited for the…
Read moreFound Blown Low Voltage Circuit Fuse
On 6/14/2023 Found blown low voltage circuit fuse. Stripped thermostat wire at the RTU and Thermostat. Installed new thermostat as y1 switch was stuck open. Monitored unit bring room temp down to 70* in Austin Texas. Near Wall Street Austin, Texas 78754 Check out the Areas We Serve and jobs we are doing by clicking:…