Found 2 Liquid Line Driers Installed

On 4/12/2023 Found suction sitting under 5psi. Box temp at 27*f upon arrival. Went to condenser and found 2 liquid line driers installed. Sight glass flashing but head pressure sitting at a 100*f condensing temperature 72*f outside. Took out double driers and installed a new drier and sight glass. Pulled vacuum. Opened system. Suction pressure…
Read more

Jump Out the Auxiliary Connected to the Compressor Contactor

On 4/10/2023 I jump out the auxiliary connected to the compressor contactor, the defrost contactor coil pulls in. Deiced coil and turned system back on. Ran through defrost. System still didn’t pump down. Checked defrost clock voltages. 208 to timer motor. 120v out of “3” when in defrost. 120v out of “4” no matter if…
Read more

Cleaned all Self-Contained Unit Condensers

On 4/7/2023 Cleaned all self-contained unit condensers inside kitchen and at both inside bars. Unclogged the drain lines of two of these units with nitrogen in Pflugerville Texas. Near TX-130 Service Rd Pflugerville, Texas 78660 Check out the Areas We Serve and jobs we are doing by clicking: https://prorefrigerate.com/areas-we-serve/ [spacer][SHORTCODE_ELEMENTOR id=3505]
Read more

Replaced Defrost Temperature T-Stat

On 4/5/2023 After deicing coil, turned defrost on with the X terminal disconnected. The clock functioned correctly. Replaced defrost temperature T-Stat in Round Rock Texas. Near E Anderson Ave Round Rock, Texas 78664 Check out the Areas We Serve and jobs we are doing by clicking: https://prorefrigerate.com/areas-we-serve/ [spacer][SHORTCODE_ELEMENTOR id=3505]