Pro Refrigeration LLC

Moved Sensor to Return Air

Moved sensor to return air. Gaskets good seal 99% very small gap top corner of doors on center post. Condensation around doors is environmentally caused. Controller differential set at 8 degrees adjusted differential to 4 degrees and set fan for continuous on for off cycle defrost. Box pulling down to 33 degrees and cycling off and on at 37.4 degrees on 5/2/24 in Round Rock Texas.

Near Steam Way Round Rock, Texas 78665

Check out the Areas We Serve and jobs we are doing by clicking: https://prorefrigerate.com/areas-we-serve/
Moved sensor to return air

Servicing: From Temple to San Marcos Marble Falls to La Grange. And all the areas in-between.

Give us a call, you will be glad you did!

    Leave a Reply

    Your email address will not be published. Required fields are marked *