Moved sensor to return air. Gaskets good seal 99% very small gap top corner of doors on center post. Condensation around doors is environmentally caused. Controller differential set at 8 degrees adjusted differential to 4 degrees and set fan for continuous on for off cycle defrost. Box pulling down to 33 degrees and cycling off and on at 37.4 degrees on 5/2/24 in Round Rock Texas.