Repaired TXV Not Insulated
On 5/16/2023 Repaired TXV not insulated and in direct line with airflow from the condenser. High pressure switch set to 400 psi. Low pressure switch set to 5psi out 30psi cut in. Left pressure switch how it was upon arrival. Monitored system pressures until 32*f glycol temp reached in Austin Texas.