Pro Refrigeration LLC

Jump Out the Auxiliary Connected to the Compressor Contactor

On 4/10/2023 I jump out the auxiliary connected to the compressor contactor, the defrost contactor coil pulls in. Deiced coil and turned system back on. Ran through defrost. System still didn’t pump down. Checked defrost clock voltages. 208 to timer motor. 120v out of “3” when in defrost. 120v out of “4” no matter if system was in defrost or not. Changed out defrost clock. Checked pump down during defrost and during freeze cycle with a satisfied thermostat. Everything checks out okay now in Georgetown Texas.

Near W University Ave Georgetown, Texas 78628

Check out the Areas We Serve and jobs we are doing by clicking: https://prorefrigerate.com/areas-we-serve/
jump out the auxiliary connected to the compressor contactor

Servicing: From Temple to San Marcos Marble Falls to La Grange. And all the areas in-between.

Give us a call, you will be glad you did!