Pro Refrigeration LLC

Found Evap Completely Iced Over

On 6/28/2023 Found evap completely iced over. Emptied unit and deiced. Put unit back together and turned on. Found thermostat set to 9 and evap motor turning off and thermostat satisfy. Hardwired evap motor to always run and help deice coil during the off cycle. Set thermostat to 2 and watched box temp reach 37*f and turn off. Customer is happy with that in Austin Hill Texas.

Near Duval St Austin, Texas 78705

Check out the Areas We Serve and jobs we are doing by clicking: https://prorefrigerate.com/areas-we-serve/
Found evap completely iced over

Servicing: From Temple to San Marcos Marble Falls to La Grange. And all the areas in-between.

Give us a call, you will be glad you did!