On 88/16/2023 found that the hose for the inlet had a cut in it. I cut the part out and re-put it in the inlet valve. Ice machine is working. The distributor was cracked so I replaced with new distributor in Austin Texas. Near W Powell Ln Austin, Texas 78753 Check out the Areas We…
Read moreRefrigerant Leak Coming Out of a Copper Bend
On 8/14/2023 When charging system back up I found a refrigerant leak coming out of a copper bend from the condensation pan/ discharge line. Located exact spot and solders shut. Monitored system until box temp reached below 32*f in Austin Texas. Near Great Hills Trl Austin, Texas 78759 Check out the Areas We Serve and…
Read moreInstalled a Universal Start Capacitor
On 8/12/2023 Arrived on site and found that the start capacitor was bad on the compressor. I tested the compressor to make sure that it was good. Compressor is good run caps good I installed a universal start capacitor in Lakeway Texas. Near RR 620 Lakeway, Texas 78734 Check out the Areas We Serve and…
Read moreRinsed Coil Twice Because it was Very Greasy
On 8/11/2023 Unit was cool when arrived. Put in cover over top door to stimulate pans. Put in temp probe Found plastic bag and grease covering condenser coil. Degreased and rinsed coil twice because it was very greasy. Saw 30-32 as I left in Austin Texas. Near San Jacinto Boulevard Austin, Texas 78701 Check out…
Read more